Will it no longer be used? 220V emergency lighting and evacuation indication luminaires will basically be phased out!
根据《消防应急照明和疏散指示系统技术标准》GB51309-2018有关规定:
设置在距地面8m及以下的灯具的电压等级及供电方式应符合下列规定:
1)应选择A型灯具;
2) Marking lights installed on the ground shall be selected as Type A luminaires with centralized power supply;
3) For residential buildings without a fire control room, self-powered Type B luminaires may be selected for evacuation corridors, stairwells, and other areas.
Type B luminaires refer to fire emergency and evacuation indication luminaires operating at ordinary voltage (AC220V).
According to this regulation, Type B luminaires still have some usage space, meaning that residential buildings, evacuation corridors, stairwells, etc., without a fire control room (fire automatic alarm system) can still use them.
However, after the release of the relevant mandatory national standards general specifications, Type B luminaires have basically lost their market.

"General Code for Electrical and Intelligent Building" is a national standard, numbered GB 55024-2022, effective from October 1, 2022. This code is a mandatory engineering construction code; all provisions must be strictly enforced. Where relevant provisions in current engineering construction standards are inconsistent with this code, the provisions of this code shall prevail.
It is already very clear that when the "General Code for Electrical and Intelligent Building" conflicts with other codes, this code shall prevail! The following section of this code now begins to "take action"!
Article 4.5.4 of GB 55024-2022 "General Code for Electrical and Intelligent Building" clearly states:

That is, fire emergency lighting and evacuation indication signs installed at heights of 2.5m or below must be powered by safety extra-low voltage, meaning only Type A Luminaire can be used.
Since this code became mandatory on October 1st, Type B Luminaire can only be used in places where the installation height exceeds 2.5m and no fire control room is set up, essentially pushing them towards obsolescence.
Appendix: Differences between Type A and Type B fire emergency luminaires
The difference between Type A and Type B fire emergency lighting luminaires is actually their operating voltage.
Type A fire emergency luminaire: A fire emergency luminaire with a rated working voltage of the main power supply and battery power supply not exceeding DC36V.
Type B fire emergency luminaire: A fire emergency luminaire with a rated working voltage of the main power supply and battery power supply greater than DC36V or AC36V.
Source: Internet, compiled by Fire Engineering
China Light
The official website of the China Association of Lighting Industry and a full-media platform for the lighting sector. We provide authoritative and timely lighting information while striving to be a growth partner for businesses. From brand promotion and channel expansion to consulting, talent training and participation in standards development, we provide comprehensive professional services to help businesses improve quality and efficiency and jointly advance the high-quality development of the lighting industry.